Portfolio piece

Pecos, TX · commissioned 2021

Blue Bluff Solar

AC capacity
40 MW
DC capacity
53 MW
DC/AC ratio
1.32
PPA
$41/MWh
Hardware
16 inverters, 352 strings

Energy delivered

4.5 GWh

Jun 16 – 29, 2026

Performance index

99.8%

Actual ÷ expected while measured

Lost revenue

$449

$449 recoverable

Clipped by inverters

42.6 MWh

A design choice (DC/AC ratio), not a fault

Wash or wait?

Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.

$
days

Until the scheduled wash (every 90 days)

Soiling station
98.9% clean, losing 0.34%/day
Last heavy rain (≥ 6 mm)
Jun 12 (17 days ago)
Soiling since
Jun 27
Will rain help?
Next heavy rain likely within ~20 days
Soiling now
$80/day
Pays back in
69 days
Net over 2 days
−$79,894
Verdict
WaitSkip the wash in 2 days: saves $69.9K

Soiling is costing $80 a day and rising about $46 a day as dust keeps settling. Over the next 2 days a wash would recover only $206 of its $80,100 cost. The scheduled wash in 2 days isn't worth it yet either: skipping it saves about $69,902.

Other things to check

Nothing at Blue Bluff Solar above the noise floor.

Soiling and rain

What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.

Daily energy

This site's metered output against the physics model's expectation.

  • Expected (physics model)
  • Actual (metered)
0100 MWh200 MWh300 MWh400 MWhJun 16Jun 19Jun 21Jun 24Jun 26Jun 29

Where the revenue went

Energy lost to each cause, priced at each site's PPA rate.

  • Soiling

    6.0 MWh

    $246
  • String offline

    4.2 MWh

    $173
  • String degraded

    743 kWh

    $30
  • Inverter outage

    0 kWh

    $0
  • CurtailmentNot recoverable

    0 kWh

    $0

Underperforming strings

Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.

Underperforming strings
InverterStringOutput vs siblingsLikely cause
Inverter 07String 1188%Degraded

Inverters

The hardware at this site.

Inverters
InverterAC ratingDC capacityDC/ACStrings
Inverter 012.5 MW3.3 MW1.3222
Inverter 022.5 MW3.3 MW1.3222
Inverter 032.5 MW3.3 MW1.3222
Inverter 042.5 MW3.3 MW1.3222
Inverter 052.5 MW3.3 MW1.3222
Inverter 062.5 MW3.3 MW1.3222
Inverter 072.5 MW3.3 MW1.3222
Inverter 082.5 MW3.3 MW1.3222
Inverter 092.5 MW3.3 MW1.3222
Inverter 102.5 MW3.3 MW1.3222
Inverter 112.5 MW3.3 MW1.3222
Inverter 122.5 MW3.3 MW1.3222
Inverter 132.5 MW3.3 MW1.3222
Inverter 142.5 MW3.3 MW1.3222
Inverter 152.5 MW3.3 MW1.3222
Inverter 162.5 MW3.3 MW1.3222