Portfolio piece

Estevan, SK · commissioned 2024

Sage Crossing Solar

AC capacity
18.9 MW
DC capacity
22.2 MW
DC/AC ratio
1.18
PPA
$63/MWh
Hardware
6 inverters, 132 strings

Energy delivered

746 MWh

Jun 23 – 29, 2026

Performance index

97.8%

Actual ÷ expected while measured

Lost revenue

$1.0K

$1.0K recoverable

Clipped by inverters

0 kWh

A design choice (DC/AC ratio), not a fault

Wash or wait?

Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.

$
days

Until the next likely heavy rain

Soiling station
99.9% clean
Last heavy rain (≥ 6 mm)
Jun 16 (13 days ago)
Soiling since
No soiling now
Will rain help?
Nothing to wash off
Soiling now
—
Pays back in
—
Net over 6 days
—
Verdict
Nothing to wash

No soiling above the noise floor in the last 3 days (Jun 27 – 29, 2026), so a wash wouldn't recover anything.

Other things to check

  • Inverter outage: $281/day. Send a technician to reset or repair the inverter.
  • String offline: $31/day. Send a technician; the strings table below names which one.

Soiling and rain

What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.

Daily energy

This site's metered output against the physics model's expectation.

  • Expected (physics model)
  • Actual (metered)
050.0 MWh100 MWh150 MWhJun 23Jun 24Jun 25Jun 27Jun 28Jun 29

Where the revenue went

Energy lost to each cause, priced at each site's PPA rate.

  • Inverter outage

    13.4 MWh

    $842
  • String degraded

    1.6 MWh

    $103
  • String offline

    1.5 MWh

    $92
  • Soiling

    32 kWh

    $2
  • CurtailmentNot recoverable

    0 kWh

    $0

Underperforming strings

Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.

Underperforming strings
InverterStringOutput vs siblingsLikely cause
Inverter 03String 1372%Degraded
Inverter 03String 1876%Degraded

Inverters

The hardware at this site.

Inverters
InverterAC ratingDC capacityDC/ACStrings
Inverter 013.2 MW3.7 MW1.1822
Inverter 023.2 MW3.7 MW1.1822
Inverter 033.2 MW3.7 MW1.1822
Inverter 043.2 MW3.7 MW1.1822
Inverter 053.2 MW3.7 MW1.1822
Inverter 063.2 MW3.7 MW1.1822