Estevan, SK · commissioned 2024
Sage Crossing Solar
- AC capacity
- 18.9 MW
- DC capacity
- 22.2 MW
- DC/AC ratio
- 1.18
- PPA
- $63/MWh
- Hardware
- 6 inverters, 132 strings
Energy delivered
1.6 GWh
Jun 16 – 29, 2026
Performance index
95.4%
Actual ÷ expected while measured
Lost revenue
$4.9K
$4.9K recoverable
Clipped by inverters
0 kWh
A design choice (DC/AC ratio), not a fault
Wash or wait?
Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.
Until the next likely heavy rain
- Soiling station
- 99.9% clean
- Last heavy rain (≥ 6 mm)
- Jun 16 (13 days ago)
- Soiling since
- No soiling now
- Will rain help?
- Nothing to wash off
- Soiling now
- —
- Pays back in
- —
- Net over 6 days
- —
- Verdict
- Nothing to wash
No soiling above the noise floor in the last 3 days (Jun 27 – 29, 2026), so a wash wouldn't recover anything.
Other things to check
- Inverter outage: $281/day. Send a technician to reset or repair the inverter.
- String offline: $31/day. Send a technician; the strings table below names which one.
Soiling and rain
What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.
Heavy rain (≥ 6 mm) Showers
Daily energy
This site's metered output against the physics model's expectation.
- Expected (physics model)
- Actual (metered)
Where the revenue went
Energy lost to each cause, priced at each site's PPA rate.
- Inverter outage
72.9 MWh
$4.6K - String degraded
3.3 MWh
$209 - String offline
1.5 MWh
$92 - Soiling
50 kWh
$3 - CurtailmentNot recoverable
0 kWh
$0
Underperforming strings
Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.
| Inverter | String | Output vs siblings | Likely cause |
|---|---|---|---|
| Inverter 03 | String 13 | 72% | Degraded |
| Inverter 03 | String 18 | 76% | Degraded |
Inverters
The hardware at this site.
| Inverter | AC rating | DC capacity | DC/AC | Strings |
|---|---|---|---|---|
| Inverter 01 | 3.2 MW | 3.7 MW | 1.18 | 22 |
| Inverter 02 | 3.2 MW | 3.7 MW | 1.18 | 22 |
| Inverter 03 | 3.2 MW | 3.7 MW | 1.18 | 22 |
| Inverter 04 | 3.2 MW | 3.7 MW | 1.18 | 22 |
| Inverter 05 | 3.2 MW | 3.7 MW | 1.18 | 22 |
| Inverter 06 | 3.2 MW | 3.7 MW | 1.18 | 22 |