Vulcan, AB · commissioned 2019
Stony Valley Solar
- AC capacity
- 69.3 MW
- DC capacity
- 82.8 MW
- DC/AC ratio
- 1.19
- PPA
- $57/MWh
- Hardware
- 22 inverters, 528 strings
Energy delivered
13.1 GWh
Jun 1 – 29, 2026
Performance index
98.8%
Actual ÷ expected while measured
Lost revenue
$8.8K
$8.8K recoverable
Clipped by inverters
0 kWh
A design choice (DC/AC ratio), not a fault
Wash or wait?
Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.
Rain won't help, so up to 90 days
- Soiling station
- 95.3% clean, losing 0.42%/day
- Last heavy rain (≥ 6 mm)
- Jun 26 (3 days ago)
- Soiling since
- Jun 19
- Will rain help?
- Soiling survived a heavy rain: rain won't clear it
- Soiling now
- $1,429/day
- Pays back in
- 35 days
- Net over 90 days
- $277,508
- Verdict
- Clean now
Soiling is costing $1,429 a day and rising about $121 a day as dust keeps settling. Over the next 90 days a wash recovers about $399,908: $277,508 more than it costs, and waiting for rain won't help.
Other things to check
Nothing at Stony Valley Solar above the noise floor.
Soiling and rain
What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.
Heavy rain (≥ 6 mm) Showers
Daily energy
This site's metered output against the physics model's expectation.
- Expected (physics model)
- Actual (metered)
Where the revenue went
Energy lost to each cause, priced at each site's PPA rate.
- Soiling
150 MWh
$8.6K - String degraded
4.1 MWh
$236 - Inverter outage
0 kWh
$0 - CurtailmentNot recoverable
0 kWh
$0 - String offline
0 kWh
$0
Underperforming strings
Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.
| Inverter | String | Output vs siblings | Likely cause |
|---|---|---|---|
| Inverter 21 | String 10 | 79% | Degraded |
Inverters
The hardware at this site.
| Inverter | AC rating | DC capacity | DC/AC | Strings |
|---|---|---|---|---|
| Inverter 01 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 02 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 03 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 04 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 05 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 06 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 07 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 08 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 09 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 10 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 11 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 12 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 13 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 14 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 15 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 16 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 17 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 18 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 19 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 20 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 21 | 3.2 MW | 3.8 MW | 1.19 | 24 |
| Inverter 22 | 3.2 MW | 3.8 MW | 1.19 | 24 |