Portfolio piece

Imperial Valley, CA · commissioned 2023

Iron Hollow Solar

AC capacity
15 MW
DC capacity
18.2 MW
DC/AC ratio
1.21
PPA
$48/MWh
Hardware
6 inverters, 102 strings

Energy delivered

1.4 GWh

Jun 16 – 29, 2026

Performance index

88.8%

Actual ÷ expected while measured

Lost revenue

$8.8K

$8.8K recoverable

Clipped by inverters

847 kWh

A design choice (DC/AC ratio), not a fault

Wash or wait?

Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.

$
days

Until the scheduled wash (every 60 days)

Soiling station
87.1% clean, losing 0.27%/day
Last heavy rain (≥ 6 mm)
None on record
Soiling since
Jun 1
Will rain help?
Heavy rain is rare here in this season
Soiling now
$667/day
Pays back in
38 days
Net over 13 days
−$26,599
Verdict
WaitKeep the wash in 13 days

Soiling is costing $667 a day and rising about $16 a day as dust keeps settling. Over the next 13 days a wash would recover only $9,901 of its $36,500 cost, and the scheduled wash in 13 days will clean the panels anyway.

Other things to check

Nothing at Iron Hollow Solar above the noise floor.

Soiling and rain

What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.

Daily energy

This site's metered output against the physics model's expectation.

  • Expected (physics model)
  • Actual (metered)
050.0 MWh100 MWh150 MWhJun 16Jun 19Jun 21Jun 24Jun 26Jun 29

Where the revenue went

Energy lost to each cause, priced at each site's PPA rate.

  • Soiling

    179 MWh

    $8.6K
  • String degraded

    3.4 MWh

    $164
  • Inverter outage

    0 kWh

    $0
  • CurtailmentNot recoverable

    0 kWh

    $0
  • String offline

    0 kWh

    $0

Underperforming strings

Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.

Underperforming strings
InverterStringOutput vs siblingsLikely cause
Inverter 06String 0484%Degraded
Inverter 03String 1484%Degraded

Inverters

The hardware at this site.

Inverters
InverterAC ratingDC capacityDC/ACStrings
Inverter 012.5 MW3 MW1.2117
Inverter 022.5 MW3 MW1.2117
Inverter 032.5 MW3 MW1.2117
Inverter 042.5 MW3 MW1.2117
Inverter 052.5 MW3 MW1.2117
Inverter 062.5 MW3 MW1.2117

Rendered from ClickHouse via GraphQL: 14 SQL queries reading 4.5M rows, 482 ms end to end (1170 ms of query time, some of it in parallel). How this works