Medicine Hat, AB · commissioned 2023
Granite Point Solar
- AC capacity
- 43.2 MW
- DC capacity
- 50.3 MW
- DC/AC ratio
- 1.16
- PPA
- $63/MWh
- Hardware
- 12 inverters, 276 strings
Energy delivered
3.9 GWh
Jun 16 – 29, 2026
Performance index
95.9%
Actual ÷ expected while measured
Lost revenue
$10.6K
$10.6K recoverable
Clipped by inverters
0 kWh
A design choice (DC/AC ratio), not a fault
Wash or wait?
Based on the last 3 days (Jun 27 – 29, 2026) and the site's soiling station. A wash has to pay for itself before the next likely heavy rain or scheduled wash; type in a contractor's quote or your own window to change the answer.
Rain won't help, so up to 90 days
- Soiling station
- 94.7% clean, losing 0.19%/day
- Last heavy rain (≥ 6 mm)
- Jun 13 (16 days ago)
- Soiling since
- Jun 3
- Will rain help?
- Soiling survived a heavy rain: rain won't clear it
- Soiling now
- $1,025/day
- Pays back in
- 45 days
- Net over 90 days
- $91,879
- Verdict
- Clean now
Soiling is costing $1,025 a day and rising about $34 a day as dust keeps settling. Over the next 90 days a wash recovers about $168,279: $91,879 more than it costs, and waiting for rain won't help.
Other things to check
- String offline: $70/day. Send a technician; the strings table below names which one.
Soiling and rain
What soiling cost each day, above what fell from the sky. Soiling that drops to zero after a heavy rain (6 mm or more) was washed off; soiling that carries on through one needs a crew.
Heavy rain (≥ 6 mm) Showers
Daily energy
This site's metered output against the physics model's expectation.
- Expected (physics model)
- Actual (metered)
Where the revenue went
Energy lost to each cause, priced at each site's PPA rate.
- Soiling
159 MWh
$10.0K - String offline
8.6 MWh
$541 - Inverter outage
206 kWh
$13 - CurtailmentNot recoverable
0 kWh
$0 - String degraded
0 kWh
$0
Underperforming strings
Below 93% of their siblings' output per kW, Jun 23 – 29, 2026.
| Inverter | String | Output vs siblings | Likely cause |
|---|---|---|---|
| Inverter 12 | String 05 | 40% | Degraded |
Inverters
The hardware at this site.
| Inverter | AC rating | DC capacity | DC/AC | Strings |
|---|---|---|---|---|
| Inverter 01 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 02 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 03 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 04 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 05 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 06 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 07 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 08 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 09 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 10 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 11 | 3.6 MW | 4.2 MW | 1.16 | 23 |
| Inverter 12 | 3.6 MW | 4.2 MW | 1.16 | 23 |
Rendered from ClickHouse via GraphQL: 14 SQL queries reading 6M rows, 620 ms end to end (2037 ms of query time, some of it in parallel). How this works